50PG03---07
Single Package Rooftop Units
Electric Cooling with PURONR (R---410A)
Refrigerant and COMFORTLinkt Controls
Installation Instructions
IMPORTANT: This installation instruction contains basic unit
installation information including installation of field control
devices. For information on unit start--up, service, and operation,
refer to the unit Controls, Start-- Up, Operation, Service, and
Troubleshooting Instructions also enclosed in the unit literature
packet.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
TABLE OF CONTENTS
Before performing service or maintenance operations
on unit, turn off main power switch to unit and install
lockout tag.
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Step 1 -- Provide unit Support . . . . . . . . . . . . . . . . . . . . . . . . . 4
Step 2 -- Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Step 3 -- Field Fabricate Ductwork . . . . . . . . . . . . . . . . . . . . . . 7
Step 4 -- Make Unit Duct Connections . . . . . . . . . . . . . . . . . . . 7
Step 5 -- Install External Trap for Condensate Drain . . . . . . . . 7
Step 6 -- Make Electrical Connections . . . . . . . . . . . . . . . . . . . 8
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Puron (R--410a) refrigerant systems operate at higher
pressures than standard R--22 systems. Do not use R--22
service equipment or components on Puron refrigerant
equipment.
Step 7 -- Install Outdoor Air Hoods (Units With
Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Step 8 -- Install All Accessories . . . . . . . . . . . . . . . . . . . . . . . 22
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or
service air-conditioning equipment.
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Untrained personnel can perform the basic maintenance functions
of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions
in the literature, tags and labels attached to the unit, and other
safety precautions that may apply.
1. Improper installation, adjustment, alteration, service,
or maintenance can cause property damage, personal
injury, or loss of life. Refer to the User’s Information
Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
Follow all safety codes. Wear safety glasses and work gloves.
Recognize safety information. This is the safety--alert symbol
.
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
IMPORTANT: Units have high ambient operating limits. If limits
are exceeded, the units will automatically lock the compressor out
of operation. Manual reset will be required to restart the
compressor.
3
Positioning
INSTALLATION
Step 1 — Provide Unit Support
Roof Curb
Maintain clearance, per Fig. 2, around and above unit to provide
minimum distance from combustible materials, proper airflow, and
service access. See Fig. 4 for location of access panels.
Assemble or install accessory roof curb in accordance with
instructions shipped with this accessory. (See Fig. 1.) Install
insulation, cant strips, roofing, and counter flashing as shown.
Ductwork can be installed to roof curb before unit is set in place.
Ductwork must be attached to curb and not to the unit. Curb must
be level. This is necessary to permit unit drain to function properly.
Unit leveling tolerance is 1/16--in. per linear ft in any direction.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required. When accessory roof curb is
used, unit may be installed on class A, B, or C roof covering
material. Carrier roof curb accessories are for flat roofs or slab
mounting.
Do not install unit in an indoor location. Do not locate air inlets
near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from higher
level runoff and overhangs.
After unit is in position, remove crating and polyethylene sheet.
Roof Mount
Check building codes for weight distribution requirements. Unit
operating weight is shown in Table 1.
Installation Onto Curb
The 50PG units are designed to fit on the accessory full perimeter
curb. In either case, correct placement of the unit onto the curb is
critical to operating performance. To aid in correct positioning,
place unit on roof curb to maintain 1/4--in. gap between the inside
of rail and roof curb on long sides and a 1/2--in. gap between the
inside of rail and roof curb on both duct and condenser ends. Refer
to Fig. 1 and 3, to assure proper duct opening alignment.
IMPORTANT: The gasketing of the unit to the roof curb is critical
for a watertight seal. Install gasket with the roof curb as shown in
Fig. 1. Improperly applied gasket can also result in air leaks and
poor unit performance. Do not slide unit to position on roof curb.
Alternate Unit Support
NOTE: Before positioning unit onto curb, refer to Step 5 -- Install
External Trap for Condensate Drain section concerning bottom
drain connection plug.
When a curb cannot be used, install unit on a noncombustible
surface. Support unit with sleepers, using unit curb support area. If
sleepers cannot be used, support long sides of unit with a minimum
of 3 equally spaced 4--in. x 4--in. pads on each side.
Step 2 — Rig and Place Unit
Inspect unit for transportation damage. See Table 1 for physical
data. File any claim with transportation agency.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
!
CAUTION
Do not slide unit to position when it is sitting on the curb.
Curb gasketing material may be damaged and leaks may
result.
PERSONAL INJURY AND PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to roof.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6--in.
beyond unit cabinet. Install
condenser--coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
a
gravel apron in front of
Do not drop unit; keep upright. Use spreader bars over unit to
prevent sling or cable damage. Rollers may be used to move unit
across a roof. Level by using unit rail as a reference; leveling
tolerance is ± 1/16--in. per linear ft in any direction. See Fig. 3 for
additional information. Unit rigging weight is shown in Fig. 3.
Rigging holes are provided in the unit base rails as shown in Fig. 3.
Refer to rigging instructions on unit.
CAUTION-NOTICE TO RIGGERS:
ACCESS PANEL MUST BE IN PLACE WHEN RIGGING.
Hook rigging shackles through holes in base rail, as shown in
Detail A. Holes in base rails are centered around the unit
center of gravity. Use wooden top skid, when rigging, to
prevent rigging straps from damaging unit.
A
B
C
D
E
MAX. WEIGHT
UNIT
SIZE
in.
mm
in.
mm
in.
mm
in.
mm
in.
mm
lb
kg
03-07
77.9
1978
36-54
914-1371
44.8
1139
42.0
1067
23.5
597
1156
525
C07270
Fig. 3 -- 50PG Rigging Label
4
Table 1 – Physical Data
BASE UNIT 50PG
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
Unit*
03
2
04
3
05
4
06
5
07
6
704
704
775
829
874
Economizer
Vertical
Horizontal
40
50
40
50
40
50
40
50
40
50
Humidi-MiZer™ Adaptive Dehumidification
22
22
31
27
26
System
Roof Curb
14-in.
24-in.
122
184
122
184
122
184
122
184
122
184
COMPRESSOR
Quantity
Oil Type
Number of Refrigerant Circuits
Oil (oz)
Fully Hermetic Scroll
1
1
1
1
1
Copeland 3MA
1
38
1
42
1
42
1
66
1
56
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb) — Standard Unit
R-410A (Puron® Refrigerant)
TXV
7.3
TXV
9.0
TXV
15.7
TXV
16.6
TXV
19.0
Operating Charge (lb) — Unit with
11.75
13.50
25.00
22.00
22.70
Humidi-MiZer System
CONDENSER COIL
Condenser A (Outer)
Rows...Fins/in.
Face Area (sq ft)
Condenser B (Inner)
Rows...Fins/in.
Face Area (sq ft)
Humidi-MiZer Coil
Rows...Fins/in.
Enhanced Copper Tubes, Aluminum Lanced Fins
1…17
12.6
1…17
12.6
2…17
12.6
2…17
12.6
2…17
12.6
—
—
1…17
12.6
2…17
12.6
2…17
12.6
2…17
12.6
1...17
6.4
1...17
6.4
1...17
9.3
1...17
9.3
1...17
9.3
Face Area (sq ft)
CONDENSER FAN
Quantity…Diameter (in.)
Nominal Cfm (Total, all fans)
Motor Hp
Propeller
1…24
1…24
1…24
1…24
1…24
3500
3500
3500
4500
4500
1
1
1
1
1
/
/
/
/
/
4
8
8
8
4
Nominal Rpm — High Speed
Nominal Rpm — Low Speed
EVAPORATOR COIL
Rows…Fins/in.
825
300
825
300
825
300
1100
300
1100
300
Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Face Split
2…15
9.3
2…15
9.3
2…15
9.3
3…15
9.3
4…15
9.3
Face Area (sq ft)
* See Legend on next page.
5
Table 1 — Physical Data (cont)
BASE UNIT 50PG (cont)
EVAPORATOR FAN
Quantity…Size (in.)
03
04
05
06
07
Centrifugal Type, Belt Drive
Low
High
Low
High
1...12 x 9
1...12 x 9
Belt
Belt
800
0.85
0.85
1620
48Y
1...12 x 9
1...12 x 9
Belt
Belt
1200
0.85
0.85
1620
48Y
1...12 x 9
1...12 x 9
Belt
Belt
1600
0.85
1.60/2.40†
1620
48Y
56Y
596-910
828-1173
Ball
1...12 x 9
1...12 x 9
Belt
Belt
2000
0.85/2.40†
1.60/2.40†
1725
56Y
56Y
690-978
929-1261
Ball
1...12 x 9
1...12 x 9
Belt
Belt
2400
2.40
3.10
1725
56Y
Type Drive
Nominal Cfm
Maximum Continuous Bhp
Low
High
Motor Nominal Rpm
Motor Frame Size
Low
High
Low
High
48Y
48Y
56Y
Fan Rpm Range
482-736
656-1001
Ball
482-736
796-1128
Ball
796-1128
1150-1438
Ball
Motor Bearing Type
Maximum Fan Rpm
Motor Pulley Pitch Diameter Range (in.)
2000
2000
2000
2000
2000
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
1.9-2.9
1.9-2.9
6.8
1.9-2.9
2.4-3.4
6.8
1.9-2.9
2.4-3.4
5.5
2.4-3.4
2.8-3.8
6.0
2.4-3.4
4.0-5.0
5.2
Fan Pulley Pitch Diameter (in.)
Nominal Motor Shaft Diameter (in.)
Belt...Pitch Length (in.)
5.0
5.2
5.0
5.2
6.0
1
1
1
1
1
5
5
5
5
7
/
/
/
/
/
/
/
/
/
/
2
2
2
2
2
8
8
8
8
8
49.3
49.3
AX
49.3
49.3
AX
49.3
49.3
AX
49.3
49.3
AX
49.3
52.3
AX
Belt…Type
AX
AX
AX
AX
AX
Pulley Center Line Distance Min. (in.)
Pulley Center Line Distance Max. (in.)
16.2
16.2
20.2
20.2
48
65
5
16.2
16.2
20.2
20.2
48
62
5
16.2
16.2
20.2
20.2
59
69
5
16.2
16.2
20.2
20.2
58
66
5
16.2
16.2
20.2
20.2
66
58
5
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
5
482
5
482
5
596
5
690
5
796
Factory Pulley Setting (rpm)
656
796
828
929
1150
3
3
3
3
3
Fan Shaft Diameter at Pulley (in.)
HIGH-PRESSURE SWITCH (psig)
Cutout
Reset (Auto.)
RETURN-AIR FILTERS
Quantity…Size (in.)
/
/
/
/
/
4
4
4
4
4
660 ± 10
505 ± 20
660 ± 10
505 ± 20
660 ± 10
505 ± 20
Throwaway
4…16 x 20 x 2
660 ± 10
505 ± 20
660 ± 10
505 ± 20
4…16 x 20 x 2
4…16 x 20 x 2
4…16 x 20 x 2
4…16 x 20 x 2
LEGEND
TXV --- Thermostatic Expansion Valve
* Aluminum evaporator coil/aluminum condenser coil.
{
Single phase/three phase.
6
duct covers to duct panel. Save panels. Install duct covers in the
vertical duct openings in the basepan with the insulation side up.
Covers will drop into openings and can be secured using
field--supplied self--tapping screws. Ductwork can be attached to
duct flanges provided on unit. When securing ductwork to unit, do
not drill in area below bead or above top edge of duct opening.
Step 3 — Field Fabricate Ductwork
On vertical units, secure all ducts to roof curb and building
structure. Do not connect ductwork to unit. For horizontal
applications, field--supplied flanges should be attached to
horizontal discharge openings and all ductwork secured to the
flanges. Insulate and weatherproof all external ductwork, joints,
and roof openings with counter flashing and mastic in accordance
with applicable codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be
ducted through the roof deck to comply with applicable fire codes.
Step 5 — Install External Trap for Condensate
Drain
The unit’s 3/4--in. condensate drain connections are located on the
bottom and side of the unit. If the down drain is used, drill a
3
minimum of a 5/8-in. diameter hole but not larger than a / -in.
4
diameter hole through the drain pan. A dimple of 2 mm in
diameter and 1.5 mm deep will be provided in the drain pan to help
locate the drill bit and to start the hole. Do not cut through the
PVC pipe threads. Unit discharge connections do not determine
the use of drain connections; either drain connection can be used
with vertical or horizontal applications. See Fig. 2 for locations.
When using the standard side drain connection, make sure the plug
(red) in the alternate bottom connection is tight before installing the
unit. (See Fig. 5.)
A minimum clearance is not required around ductwork. Cabinet
return--air static pressure (a negative condition) shall not exceed
0.35--in. wg with economizer or 0.45--in. wg without economizer.
Step 4 — Make Unit Duct Connections
Vertical Supply/Return Configuration
Unit is shipped in vertical supply/return configuration. Ductwork
openings are shown in Fig. 1 and 3. Attach the ductwork to the
roof curb. Do not attach duct directly to the unit.
To use the bottom drain connection for a roof curb installation,
relocate the factory--installed plug (red) from the bottom
connection to the side connection. A 1/2--in. socket extension can
be used to remove the plug. (See Fig. 5.) The piping for the
condensate drain and external trap can be completed after the unit
is in place.
All units must have an external trap for condensate drainage. Install
a trap at least 4--in. deep and protect against freezeup. If drain line
is installed downstream from the external trap, pitch the line away
from the unit at 1--in. per 10 ft of run. Do not use a pipe size
smaller than the unit connection (3/4--in.). (See Fig. 6 and 7.)
The 50PG units are provided with a removable condensate pan for
ease of cleaning. It is recommended that a union be placed between
the unit and condensate drainage to ease the removal of the pan
during servicing. Adequate clearance should be allowed if removal
of condensate pan is required. Allow 54--in. between condensate
pan access panel and any obstruction for complete removal.
!
WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal
injury.
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a
90--degree turn in the return ductwork between the unit
and the conditioned space. If a 90--degree elbow cannot
be installed, then a grille of sufficient strength and
density should be installed to prevent objects from
falling into the conditioned space.
Horizontal Supply/Return Applications
Unit can be field--converted from vertical supply/return to
horizontal supply/return. Remove all screws securing horizontal
CONTROL BOX
AND
COMPRESSOR
ELECTRICAL
OPTIONS PANEL
INDOOR MOTOR
ACCESS DOOR
OUTDOOR AIR
SCREEN
(HIDDEN)
CONDENSER COIL
ACCESS PANEL
ECONOMIZER
HOOD
ELECTRIC HEAT
ACCESS DOOR
BAROMETRIC
RELIEF DAMPER
FILTER ACCESS DOOR
HOOD
BASEPAN CONNECTIONS
ACCESS PANEL
C07272
Fig. 4 -- Panel and Filter Locations
7
INSERT SIDE DRAIN
PLUG FOR DOWN
DRAIN USE.
DRILL 5/8” DIA. (0.625 mm) HOLE
THRU FOR DOWN DRAIN USE.
C10321
Fig. 5 -- Condensate Drain Pan
OPTIONAL UNIONS
TO ALLOW FOR CONDENSATE
PAN REMOVAL
4" (102mm)
CONDENSATE
PAN ACCESS
PANEL
C06234
Fig. 6 -- External Trap for Condensate Drain
Step 6 — Make Electrical Connections
(For more details, refer to the Controls, Start--up, Operation, and
Troubleshooting manual).
Field Power Supply
All 208/230--v units are factory wired for 230--v power supply. If
the 208/230--v unit is to be connected to a 208--v power supply, the
transformers (TRAN1 and TRAN2) must be rewired by moving
the black wire with the 1/4--in. female quick connect from the
230--volt connection and moving to the 200--volt 1/4--in. male
terminal on the primary side of the transformer.
Refer to unit label diagram for additional information. Leads are
provided for field wire connections. Use UL (Underwriters
Laboratories) approved copper/aluminum connector.
NOTE: Trap should be deep enough to offset maximum unit static difference.
A 4-in. trap is recommended.
When installing rooftop units, provide safety disconnect per NEC
(National Electrical Code) Article 440 or local codes. For
non--fused disconnects, size the disconnect according to the sizing
data provided in the electrical data tables. If a fused disconnect is
used, determine the minimum size for the switch based on the
disconnect sizing data provided in the electrical data tables and
then coordinate the disconnect housing size to accommodate the
Maximum Overcurrent Protection (MOCP) device size as marked
on the unit informative plate. (See Table 2 and 3.) All field wiring
must comply with NEC and local codes. Size wire based on MCA
(Minimum Circuit Amps) on the unit informative plate. See Fig. 8
for power wiring connection to the unit leads and equipment
ground.
C06291
Fig. 7 -- Condensate Drain Piping Details
Route power and ground lines through control box end panel or
unit basepan (see Fig. 2) to connections as shown on unit wiring
diagram and Fig. 8. Factory leads may be wired directly to the
disconnect.
8
Set heat anticipator settings as follows:
!
CAUTION
Stage 1
VOLTAGE
STAGE 1 AND 2
(W1 AND W2) ON
(W1) ON
UNIT DAMAGE HAZARD
All
0.2
0.4
Failure to follow this caution may result in equipment
damage.
Settings may be changed slightly to provide a greater degree of
comfort for a particular installation.
The correct power phasing is critical to the operation of the
scroll compressors. An incorrect phasing will result in an
alarm being generated and compressor operation lockout.
Should this occur, power phase correction must be made to
the incoming power. Damage to compressor could result.
C.A1
FIELD
POWER
WIRING
FACTOR
POWER
WIRING
21
22
23
11
12
13
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
EQUIP GND
Unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of electrical wire connected to unit ground lug in
control compartment, or conduit approved for electrical
ground when installed in accordance with NEC; ANSI
(American National Standards Institute)/NFPA (National
Fire Protection Association), latest edition, and local
electrical codes.
LEGEND
C.A1 -- Compressor Contactor (A1)
EQUIP -- Equipment
GND -- Ground
NEC -- National Electrical Code
NOTE: The maximum wire size for C.A1 is 2/0.
C06237
Fig. 8 -- Field Power Wiring Connections
Field wiring must conform to temperature limitations for type “T”
wire. All field wiring must comply with NEC and local
requirements.
THERMOSTAT ASSEMB Y
REMOVABLE JUMPER
L
Operating voltage to compressor must be within voltage range
indicated on unit nameplate. On 3--phase units, voltages between
phases must be balanced within 2%.
RH
RC
Y1
Y2
W1
W2
G
C
C
X
TB1
R
Y1
Y2
W1
W2
G
X
Unit failure as a result of operation on improper line voltage or
excessive phase imbalance constitutes abuse and may cause
damage to electrical components.
ROOFTOP UNIT
Field Control Wiring (Units Without Optional
Humidi-MiZert Adaptive Dehumidification System)
C06292
Fig. 9 -- Field Control Thermostat Wiring
Unit can be controlled with either a Carrier--approved accessory
thermostat or a Carrier--approved space temperature sensor. Install
thermostat according to the installation instructions included with
accessory. Locate thermostat assembly or space temperature sensor
on a solid interior wall in the conditioned space to sense average
temperature.
Route thermostat or space temperature sensor cable or equivalent
single leads of colored wire from subbase terminals through
conduit into unit to low--voltage connections as shown on unit
label wiring diagram and in Fig. 9 or 10.
T-56 SPT
T-55 SPT
SEN
SEN
SET
RED
BLACK
WHITE
JUMPER
T55
TB1
1
2
3
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gauge) insulated wire (35_C minimum). For 50 to 75 ft, use
no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use
no. 14 AWG insulated wire (35_C Minimum). All wire larger than
no. 18 AWG cannot be directly connected at the thermostat and
will require a junction box and splice at the thermostat.
ROOFTOP UNIT
C06239
Fig. 10 -- Field Control Space Temperature Sensor Wiring
Field Control Wiring (Units With Optional Humidi-
MiZert Adaptive Dehumidification System)
Units require temperature control inputs for cooling and heating
operation and humidity control inputs for Humidi--MiZer
operation.
9
Temperature Control
Controls, Start--up, Operation and Troubleshooting manual for
configuration.
The unit can be controlled with either a Carrier--approved space
temperature sensor, a Carrier accessory Thermidistatt device, or a
Carrier--approved accessory thermostat. Install the temperature
control device according to the installation instructions included
with the accessory. Locate the device on a solid interior wall in the
conditioned space to sense average temperature. Carrier space
temperature sensor wiring connections are shown in Fig. 10.
General thermostat field control wiring connections are shown in
Fig. 9. Carrier Thermidistat device wiring connections are shown
in Fig. 11. Configuration of the unit control is required to specify
the control input type before unit operation.
Route thermostat or space temperature sensor cable or equivalent
single leads of colored wire from subbase terminals through
conduit into unit to low--voltage connections as shown on unit
label wiring diagram and in Fig. 9--11.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gauge) insulated wire (35_C minimum). For 50 to 75 ft, use
no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use
no. 14 AWG insulated wire (35_C Minimum). All wire larger than
no. 18 AWG cannot be directly connected at the thermostat and
will require a junction box and splice at the thermostat.
Units with the Humidi--MiZert option receive a discrete input
from a field--installed device (such as from the Carrier humidistat
or Thermidistat device). The discrete input is connected to the TB1
terminal strip points labeled Humidistat 1 and 2. As this is a
discrete input, one of the connection points is for power to the
switch and the other is the return path. (See Fig. 12.)
A space relative humidity sensor input (SP.RH) is only available if
an economizer board (ECB) is installed in the unit and then the
sensor can be connected to the OAQ point TB1--4. (See Fig. 12.)
This input is used instead of the discrete humidistat or thermidistat
inputs. The input controls the Humidi--MiZer using the 4 to 20 mA
as percent humidity. The relative humidity value (measured by the
relative humidity sensor) can be displayed on the Scrolling
Marquee, in the space through a System Pilott device, or can be
read by other CCN devices where it can be used to perform more
advanced functions. The humidity sensor must be configured
correctly; refer to the Controls, Start--up, Operation, and
Troubleshooting manual for details.
If the customer also wishes to install a smoke detector into a
Humidi--MiZer equipped 50PG unit, the fire shutdown connection
points are on Plug PL--19, located in the economizer section. See
the unit wiring schematic for wiring. For third--party smoke
detector, see Fig. 13.
Set heat anticipator settings as follows:
Stage 1
STAGE 1 AND 2
(W1 AND W2) ON
VOLTAGE
All
(W1) ON
Point 19--3 is the 24 vac power source for the detector and point
19--5 is the 24 vac signal input for fire shutdown.
0.2
0.4
More information is available in the third party control section of
the Controls, Start--up, Operation, and Troubleshooting manual.
Settingsmay be changed slightly to provide a greater degree of
comfort for a particular installation.
Humidity Control
THERMIDISTAT
G
G
C
C
DEHUM
OC
R
R
Y1
Y1
Y2
Y2
W1
W1
W2
W2
Unit can be controlled with either a Carrier accessory Thermidistat
device or a Carrier--approved accessory humidistat (switch output).
The input for an accessory humidity sensor with 4 to 20 mA output
is another option available when an economizer board is installed.
Install the humidity control device according to the installation
instructions included with the accessory. Locate the device on a
solid interior wall in the conditioned space to sense average
humidity. Carrier Thermidistat device wiring connections are
shown in Fig. 11. General humidistat wiring connections are
shown in Fig. 12. Configuration of the unit control is required to
specify the control input type before unit operation. Refer to the
5
1
2
TB1
HUMIDISTAT
ROOFTOP UNIT
C07055
Fig. 11 -- Field Control Thermidistat Wiring
C07045
Fig. 12 -- Humidi--MiZer Low--Voltage Terminal Strip -- Humidity Sensor/Humidity Wiring
10
C07191
Fig. 13 -- Third Party Smoke Detector on Humidi--MiZert
11
Table 2 – Electrical Data -- Units Without Optional Convenience Outlet
VOLTAGE
RANGE
DISCONNECT
SIZE
NOMINAL
COMPRESSOR
ELECTRIC HEAT
POWER SUPPLY
OFM POWER
EXHAUST
IFM
UNIT
50PG
IFM
FLA
POWER SUPPLY
Nominal
FLA
TYPE
FLA
Min Max
RLA
LRA
FLA
kW*
MCA
MOCP†
FLA
LRA
Volts-Ph-Hz
—
—
21.9/21.9
21.9/21.9
27.8/31.1
38.6/43.6
49.5/56.1
21.9/21.9
21.9/21.9
27.8/31.1
38.6/43.6
49.5/56.1
23.3/23.3
23.3/23.5
29.5/32.9
40.4/45.4
51.3/57.9
23.3/23.3
23.3/23.5
29.5/32.9
40.4/45.4
51.3/57.9
25.2/25.2
25/25
25/25
30/35
40/45
50/60
25/25
25/25
30/35
40/45
50/60
25/25
25/25
30/35
45/50
60/60
25/25
25/25
30/35
45/50
60/60
30/30
30/30
30/35
40/45
50/60
80/90
30/30
30/30
30/35
40/45
50/60
80/90
30/30
30/30
30/35
45/50
60/60
80/90
30/30
30/30
30/35
45/50
60/60
80/90
25/25
25/25
25/25
25/30
35/40
45/50
25/25
25/25
25/25
25/30
35/40
45/50
22/22
22/22
26/29
36/40
46/52
22/22
22/22
26/29
36/40
46/52
23/23
23/23
27/30
37/42
47/53
23/23
23/23
27/30
37/42
47/53
24/24
24/24
26/29
36/40
46/52
65/75
24/24
24/24
26/29
36/40
46/52
65/75
26/26
26/26
27/30
37/42
47/53
67/76
26/26
26/26
27/30
37/42
47/53
67/76
20/20
20/20
20/20
23/26
29/32
40/45
20/20
20/20
20/20
23/26
29/32
40/45
74/74
74/74
74/74
74/74
74/74
74/74
74/74
74/74
74/74
74/74
76/76
76/76
76/76
76/76
76/76
76/76
76/76
76/76
76/76
76/76
97/97
97/97
97/97
97/97
97/97
97/97
97/97
97/97
97/97
97/97
97/97
97/97
99/99
99/99
99/99
99/99
99/99
99/99
99/99
99/99
99/99
99/99
99/99
99/99
91/91
91/91
91/91
91/91
91/91
91/91
91/91
91/91
91/91
91/91
91/91
91/91
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
—
Low
High
Low
High
—
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
—
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
—
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
—
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
—
2.3/ 3.0 25.2/25.2
3.8/ 5.0 27.8/31.1
5.6/ 7.5 38.6/43.6
7.5/10.0 49.5/56.1
03
208/230-1-60
187
253
12.8
60
1.0
4.9
1.4
Low
High
Low
High
Low
High
52.0/60.0 11.3/15.0 71.1/81.1
—-
—
—
25.2/25.2
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
2.3/ 3.0 25.2/25.2
3.8/ 5.0 27.8/31.1
5.6/ 7.5 38.6/43.6
7.5/10.0 49.5/56.1
52.0/60.0 11.3/15.0 71.1/81.1
208/230-1-60
187
253
15.4
83
1.0
4.9
—
—
26.6/26.6
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
2.3/ 3.0 26.6/26.6
3.8/ 5.0 29.5/32.9
5.6/ 7.5 40.4/45.4
7.5/10.0 51.3/57.9
52.0/60.0 11.3/15.0 72.9/82.9
04
1.4
—
—
26.6/26.6
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
2.3/ 3.0 26.6/26.6
3.8/ 5.0 29.5/32.9
5.6/ 7.5 40.4/45.4
7.5/10.0 51.3/57.9
52.0/60.0 11.3/15.0 72.9/82.9
—
—
20.3/20.3
6.3/ 7.2
10.0/11.5
15.0/17.3
20.0/23.1
2.3/ 3.0 20.3/20.3
3.8/ 5.0 20.3/20.5
5.6/ 7.5 24.9/27.8
7.5/10.0 31.1/35.0
30.0/34.6 11.3/15.0 43.6/49.4
208/230-3-60
187
253
11.5
77
1.0
—
4.9
—
—
20.3/20.3
6.3/ 7.2
10.0/11.5
15.0/17.3
20.0/23.1
2.3/ 3.0 20.3/20.3
3.8/ 5.0 20.3/20.5
5.6/ 7.5 24.9/27.8
7.5/10.0 31.1/35.0
30.0/34.6 11.3/15.0 43.6/49.4
E xamp le : Sup p ly voltag e is 2 3 0 --- 3 --- 6 0
LEGEND
FLA
--- Ful l Lo a d A mp s
AB = 224 v
BC = 231 v
AC = 226 v
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
224 + 231 + 226
LRA --- Lo ck e d R o t o r A mp s
Average Voltage =
3
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
681
3
=
=
227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power
distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-
ingly.
{
Fuse or HACR circuit breaker.
4
NOTES:
% Voltage Imbalance
=
100 x
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
227
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percentage of voltage imbalance.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
max voltage deviation from average voltage
% Voltage Imbalance
= 100 x
average voltage
12
Table 2 -- Electrical Data -- Units Without Optional Convenience Outlet (cont)
VOLTAGE
RANGE
DISCONNECT
SIZE
NOMINAL
COMPRESSOR
ELECTRIC HEAT
POWER SUPPLY
OFM
FLA
POWER
EXHAUST
FLA
IFM
POWER SUPPLY
UNIT
50PG
IFM
FLA
Nominal
TYPE
Min
Max
RLA
LRA
FLA
MCA
MOCP†
FLA
LRA
Volts-Ph-Hz
kW*
—
6.3/ 7.2
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
—
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
—
21.7/21.7
21.7/21.7
21.7/22.3
26.6/29.5
32.9/36.8
45.4/51.1
21.7/21.7
21.7/21.7
21.7/22.3
26.6/29.5
32.9/36.8
45.4/51.1
9.0
25/25
25/25
25/25
30/30
35/40
50/60
25/25
25/25
25/25
30/30
35/40
50/60
15
22/22
22/22
22/22
24/27
30/34
42/47
22/22
22/22
22/22
24/27
30/34
42/47
9
93/93
93/93
93/93
93/93
93/93
93/93
93/93
93/93
93/93
93/93
93/93
93/93
42
Low
High
Low
High
Low
High
208/230-3-60
187
253
11.5
77
1.0
0.5
0.5
1.0
1.4
4.9
2.1
2.1
6.3/ 7.2
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
—
3.5
3.0
9.0
15
9
42
5.8
5.0
9.9
15
9
42
8.7
7.5
13.5
15
12
42
11.5
10.0
17.0
20
16
42
17.3
15.0
24.3
25
22
42
—
—
—
9.0
15
9
42
3.5
3.0
9.0
15
9
42
5.8
5.0
9.9
15
9
42
8.7
7.5
13.5
15
12
42
11.5
10.0
17.0
20
16
42
04
(cont)
17.3
15.0
24.3
25
22
42
460-3-60
414
518
187
506
633
253
5.1
35
—
—
9.6
15
10
43
3.5
3.0
9.6
15
10
43
5.8
5.0
10.6
15
10
43
8.7
7.5
14.3
15
13
43
11.5
10.0
17.8
20
16
43
17.3
15.0
25.0
30
23
43
0.6
—
—
9.6
15
10
43
3.5
3.0
9.6
15
10
43
5.8
5.0
10.6
15
10
43
8.7
7.5
14.3
15
13
43
11.5
10.0
17.8
20
16
43
17.3
15.0
25.0
30
23
43
—
—
8.0
15
8
37
9.2
10.0
14.1
15
13
37
Low
High
Low
High
13.9
15.0
20.0
25
18
37
—
—
—
8.0
15
8
37
9.2
10.0
14.1
15
13
37
13.9
15.0
20.0
25
18
37
575-3-60
4.3
31
—
—
9.4
15
10
39
9.2
10.0
15.9
20
15
39
13.9
15.0
21.8
25
20
39
1.4
—
—
9.4
15
10
39
9.2
10.0
15.9
20
15
39
13.9
15.0
21.8
25
20
39
—
—
31.5/ 31.5
31.5/ 31.5
38.6/ 43.6
49.5/ 56.1
71.1/ 81.1
92.8/106.1
33.6/ 33.6
33.6/ 33.8
41.3/ 46.3
52.1/ 58.8
73.8/ 83.8
95.4/108.8
32.9/ 32.9
32.9/ 32.9
40.4/ 45.4
51.3/ 57.9
72.9/ 82.9
94.5/107.9
35.0/ 35.5
35.0/ 35.5
43.0/ 48.0
53.9/ 60.5
75.5/ 85.5
97.1/110.5
24.2/24.2
24.2/24.2
24.9/27.8
31.1/35.0
43.6/49.4
56.1/63.9
24.5/24.5
24.5/24.5
25.3/28.1
31.5/35.4
44.0/49.8
56.5/64.3
25.6/25.6
25.6/25.6
26.6/29.5
32.9/36.8
45.4/51.1
57.9/65.6
25.9/25.9
25.9/25.9
27.0/29.9
33.3/37.1
45.8/51.5
58.3/66.0
35/ 35
35/ 35
40/ 45
50/ 60
80/ 90
100/110
30/30 123/123
30/30 123/123
36/40 123/123
46/52 123/123
65/75 123/123
85/98 123/123
17.3/20.0
26.0/30.0
34.7/40.0
52.0/60.0
69.3/80.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
—
Low
High
Low
High
Low
High
4.9
7.0
4.9
7.0
4.9
5.2
—
1.4
—
35/ 35 33/ 33 148/148
35/ 35 33/ 33 148/148
45/ 50 38/ 43 148/148
60/ 60 48/ 54 148/148
80/ 90 68/ 77 148/148
100/110 88/100 148/148
35/ 35
35/ 35
45/ 50
60/ 60
80/ 90
100/110
40/ 40 34/ 34 150/150
40/ 40 34/ 34 150/150
45/ 50 40/ 44 150/150
60/ 70 50/ 56 150/150
80/ 90 69/ 79 150/150
100/125 89/102 150/150
25/25
25/25
25/30
35/40
45/50
60/70
25/25
25/25
30/30
35/40
45/50
60/70
30/30
30/30
30/30
35/40
50/60
60/70
30/30
30/30
30/30
35/40
50/60
60/70
17.3/20.0
26.0/30.0
34.7/40.0
52.0/60.0
69.3/80.0
—
17.3/20.0
26.0/30.0
34.7/40.0
52.0/60.0
69.3/80.0
—
17.3/20.0
26.0/30.0
34.7/40.0
52.0/60.0
69.3/80.0
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
208/230-1-60
20.5
109
32/32 125/125
32/32 125/125
37/42 125/125
47/53 125/125
67/76 125/125
87/99 125/125
05
24/24 105/105
24/24 105/105
24/26 105/105
29/32 105/105
40/45 105/105
52/59 105/105
24/24 123/123
24/24 123/123
24/26 123/123
29/33 123/123
40/46 123/123
52/59 123/123
25/25 107/107
25/25 107/107
25/27 107/107
30/34 107/107
42/47 107/107
53/60 107/107
26/26 125/125
26/26 125/125
26/27 125/125
31/34 125/125
42/47 125/125
54/61 125/125
208/230-3-60
187
253
14.6
91
1.0
Low
4.9
5.2
High
*See Legend on next page.
13
Table 2 -- Electrical Data -- Units Without Optional Convenience Outlet (cont)
VOLTAGE
RANGE
DISCONNECT
SIZE
NOMINAL
COMPRESSOR
ELECTRIC HEAT
POWER SUPPLY
OFM
FLA
POWER
EXHAUST
FLA
IFM
POWER SUPPLY
UNIT
50PG
IFM
FLA
Nominal
TYPE
Min
Max
RLA
LRA
FLA
MCA
MOCP†
FLA
LRA
Volts-Ph-Hz
kW*
—
5.8
—
5.0
11.5
11.5
15
15
11
11
12
16
22
29
12
12
13
16
23
30
12
12
13
16
23
30
12
12
14
17
24
30
9
53
53
53
53
53
53
62
62
62
62
62
62
54
54
54
54
54
54
63
63
63
63
63
63
40
40
40
40
46
46
46
46
42
42
42
42
48
48
48
48
8.7
7.5
13.5
15
Low
High
Low
High
2.1
2.6
2.1
2.6
11.5
10.0
15.0
20.0
—
5.0
7.5
10.0
15.0
20.0
—
5.0
7.5
10.0
15.0
20.0
—
5.0
7.5
10.0
15.0
20.0
—
10.0
15.0
20.0
—
10.0
15.0
20.0
—
10.0
15.0
20.0
—
10.0
15.0
20.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
17.0
20
17.3
24.3
25
23.1
31.5
35
—
—
12.0
15
5.8
12.0
15
8.7
14.1
15
11.5
17.6
20
17.3
24.9
25
23.1
32.1
35
460-3-60
414
506
7.1
46
0.5
—
12.1
15
5.8
12.1
15
8.7
14.3
15
11.5
17.8
20
17.3
25.0
30
23.1
32.3
35
0.6
—
12.6
15
05
(cont)
5.8
12.6
15
8.7
14.9
15
11.5
18.4
20
17.3
25.6
30
23.1
32.9
35
—
9.0
15
9.2
14.1
15
13
18
24
9
Low
High
Low
High
2.1
2.0
2.1
2.0
13.9
20.0
25
18.5
25.8
30
—
—
8.9
15
9.2
14.0
15
13
18
24
10
15
20
25
10
14
20
25
13.9
19.9
20
18.5
25.6
30
575-3-60
518
633
5.1
34
0.5
—
10.4
15
9.2
15.9
20
13.9
21.8
25
18.5
27.5
30
1.4
—
10.3
15
9.2
15.8
20
13.9
21.6
25
18.5
27.4
30
—
40.0/ 40.0
40.0/ 40.0
40.0/ 43.6
49.5/ 56.1
71.1/ 81.1
45/ 45
45/ 45
45/ 45
50/ 60
80/ 90
38/38 160/160
38/38 160/160
38/40 160/160
46/52 160/160
65/75 160/160
85/98 160/160
17.3/ 20.0
26.0/ 30.0
34.7/ 40.0
52.0/ 60.0
69.3/ 80.0
86.7/100.0
—
Low
High
Low
High
4.9
7.0
4.9
7.0
92.8/106.1 100/110
18.8/25.0 114.5/131.1 125/150 105/121 160/160
—
—
42.1/ 42.1
42.1/ 42.1
42.1/ 46.3
52.1/ 58.8
73.8/ 83.8
45/ 45
45/ 45
45/ 50
60/ 60
80/ 90
41/41 185/185
41/41 185/185
41/43 185/185
48/54 185/185
68/77 185/185
88/100 185/185
17.3/ 20.0
26.0/ 30.0
34.7/ 40.0
52.0/ 60.0
69.3/ 80.0
86.7/100.0
—
17.3/ 20.0
26.0/ 30.0
34.7/ 40.0
52.0/ 60.0
69.3/ 80.0
86.7/100.0
—
17.3/ 20.0
26.0/ 30.0
34.7/ 40.0
52.0/ 60.0
69.3/ 80.0
86.7/100.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
95.4/108.8 100/110
18.8/25.0 117.1/133.8 125/150 108/123 185/185
—
06
208/230-1-60
187
253
26.9
145
1.5
41.4/ 41.4
41.4/ 41.4
41.4/ 45.4
51.3/ 57.9
72.9/ 82.9
45/ 45
45/ 45
45/ 50
60/ 60
80/ 90
40/40 162/162
40/40 162/162
40/42 162/162
47/53 162/162
67/76 162/162
87/99 162/162
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
94.5/107.9 100/110
18.8/25.0 116.3/132.9 125/150 107/122 162/162
—
1.4
43.5/ 43.5
43.5/ 43.5
43.5/ 48.0
53.9/ 60.5
75.5/ 85.5
50/ 50
50/ 50
50/ 50
60/ 70
80/ 90
42/42 187/187
42/42 187/187
42/44 187/187
50/56 187/187
69/79 187/187
89/102 187/187
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
97.1/110.5 100/125
18.8/25.0 118.9/135.5 125/150 109/125 187/187
E xamp le : Sup p ly voltag e is 2 3 0 --- 3 --- 6 0
LEGEND
FLA
--- Ful l Lo a d A mp s
AB = 224 v
BC = 231 v
AC = 226 v
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
224 + 231 + 226
3
LRA --- Lo ck e d R o t o r A mp s
Average Voltage =
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
681
3
=
=
227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power
distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-
ingly.
{
Fuse or HACR circuit breaker.
4
NOTES:
% Voltage Imbalance
=
100 x
227
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percentage of voltage imbalance.
max voltage deviation from average voltage
% Voltage Imbalance
= 100 x
average voltage
14
Table 2 -- Electrical Data -- Units Without Optional Convenience Outlet (cont)
VOLTAGE
RANGE
DISCONNECT
SIZE
NOMINAL
COMPRESSOR
ELECTRIC HEAT
POWER SUPPLY
OFM
FLA
IFM
POWER
EXHAUST
FLA
UNIT
50PG
IFM
FLA
POWER SUPPLY
Nominal
TYPE
Min
Max
RLA
LRA
FLA
MCA
MOCP†
FLA
LRA
Volts-Ph-Hz
kW*
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
28.7/28.7
28.7/28.7
28.7/28.7
31.5/35.4
44.0/49.8
56.5/64.3
69.0/78.6
28.7/28.7
28.7/28.7
28.7/28.7
31.5/35.4
44.0/49.8
56.5/64.3
69.0/78.6
30.1/30.1
30.1/30.1
30.1/30.1
33.3/37.1
45.8/51.5
58.3/66.0
70.8/80.4
30.1/30.1
30.1/30.1
30.1/30.1
33.3/37.1
45.8/51.5
58.3/66.0
70.8/80.4
13.0
30/30
30/30
30/30
35/40
45/50
60/70
70/80
30/30
30/30
30/30
35/40
45/50
60/70
70/80
35/35
35/35
35/35
35/40
50/60
60/70
80/90
35/35
35/35
35/35
35/40
50/60
60/70
80/90
15
28/28 156/156
28/28 156/156
28/28 156/156
29/33 156/156
40/46 156/156
52/59 156/156
63/72 156/156
28/28 156/156
28/28 156/156
28/28 156/156
29/33 156/156
40/46 156/156
52/59 156/156
63/72 156/156
30/30 158/158
30/30 158/158
30/30 158/158
31/34 158/158
42/47 158/158
54/61 158/158
65/74 158/158
30/30 158/158
30/30 158/158
30/30 158/158
31/34 158/158
42/47 158/158
54/61 158/158
65/74 158/158
Low
High
Low
High
Low
High
Low
High
—
1.4
—
208/230-3-60
187
253
17.6
123
1.5
5.2
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
13
13
13
16
23
30
36
13
13
13
16
23
30
36
13
13
14
17
24
30
37
13
13
14
17
24
30
37
10
13
18
24
29
10
13
18
24
29
12
14
20
25
30
12
14
20
25
30
67
67
67
67
67
67
67
67
67
67
67
67
67
67
68
68
68
68
68
68
68
68
68
68
68
68
68
68
53
53
53
53
53
53
53
53
53
53
55
55
55
55
55
55
55
55
55
55
5.8
5.0
13.0
15
8.7
7.5
14.1
15
11.5
10.0
17.6
20
17.3
15.0
24.9
25
23.1
20.0
32.1
35
28.9
25.0
39.4
40
—
—
13.0
15
5.8
5.0
13.0
15
06
(cont)
8.7
7.5
14.1
15
11.5
10.0
17.6
20
17.3
15.0
24.9
25
23.1
20.0
32.1
35
28.9
25.0
39.4
40
460-3-60
414
506
7.7
50
0.8
2.6
—
—
13.6
15
5.8
5.0
13.6
15
8.7
7.5
14.9
15
11.5
10.0
18.4
20
17.3
15.0
25.6
30
23.1
20.0
32.9
35
28.9
25.0
40.1
45
0.6
—
—
13.6
15
5.8
5.0
13.6
15
8.7
7.5
14.9
15
11.5
10.0
18.4
20
17.3
15.0
25.6
30
23.1
20.0
32.9
35
28.9
25.0
40.1
45
—
—
10.4
15
9.2
10.0
14.0
15
13.9
15.0
19.9
20
Low
High
Low
High
18.5
20.0
25.6
30
23.1
25.0
31.4
35
—
—
—
10.4
15
9.2
10.0
14.0
15
13.9
15.0
19.9
20
18.5
20.0
25.6
30
23.1
25.0
31.4
35
575-3-60
518
633
6.1
40
0.8
2.0
—
—
11.8
15
9.2
10.0
15.8
20
13.9
15.0
21.6
25
18.5
20.0
27.4
30
23.1
25.0
33.1
35
1.4
—
—
11.8
15
9.2
10.0
15.8
20
13.9
15.0
21.6
25
18.5
20.0
27.4
30
23.1
25.0
33.1
35
—
—
32.3/32.3
32.3/32.3
32.3/32.3
32.3/35.4
44.0/49.8
56.5/64.3
69.0/78.6
34.6/34.6
34.6/34.6
34.6/34.6
34.6/38.3
46.9/52.6
59.4/67.1
71.9/81.5
35/35
35/35
35/35
35/40
45/50
60/70
70/80
35/35
35/35
35/35
35/40
50/60
60/70
80/90
31/31 182/182
31/31 182/182
31/31 182/182
31/33 182/182
40/46 182/182
52/59 182/182
63/72 182/182
34/34 208/208
34/34 208/208
34/34 208/208
34/35 208/208
43/48 208/208
55/62 208/208
66/75 208/208
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
Low
5.2
7.5
07
208/230-3-60
187
253
20.5
149
1.5
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
High
* See Legend on next page.
15
Table 2 -- Electrical Data -- Units Without Optional Convenience Outlet (cont)
VOLTAGE
RANGE
DISCONNECT
SIZE
NOMINAL
COMPRESSOR
ELECTRIC HEAT
POWER SUPPLY
OFM
FLA
IFM
POWER
EXHAUST
FLA
UNIT
50PG
IFM
FLA
POWER SUPPLY
Nominal
TYPE
Min
Max
RLA
LRA
FLA
MCA
MOCP†
FLA
LRA
Volts-Ph-Hz
kW*
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
5.0
7.5
10.0
15.0
20.0
25.0
—
5.0
7.5
10.0
15.0
20.0
25.0
—
5.0
7.5
10.0
15.0
20.0
25.0
—
5.0
7.5
10.0
15.0
20.0
25.0
—
10.0
15.0
20.0
25.0
30.0
—
10.0
15.0
20.0
25.0
30.0
—
10.0
15.0
20.0
25.0
30.0
—
10.0
15.0
20.0
25.0
30.0
33.7/33.7
33.7/33.7
33.7/33.7
33.7/37.1
45.8/51.5
58.3/66.0
70.8/80.4
36.0/36.0
36.0/36.0
36.0/36.0
36.1/40.0
48.6/54.4
61.1/68.9
73.6/83.3
15.4
35/35
35/35
35/35
35/40
50/60
60/70
80/90
40/40
40/40
40/40
40/45
50/60
70/70
80/90
20
33/33 184/184
33/33 184/184
33/33 184/184
33/34 184/184
42/47 184/184
54/61 184/184
65/74 184/184
36/36 210/210
36/36 210/210
36/36 210/210
36/37 210/210
45/50 210/210
56/63 210/210
68/77 210/210
Low
High
Low
High
Low
High
5.2
7.5
2.6
3.4
2.6
3.4
208/230-3-60
187
253
20.5
149
1.5
1.4
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
15
15
15
16
23
30
36
16
16
16
17
24
30
37
16
16
16
17
24
30
37
17
17
17
18
24
31
38
12
13
18
24
29
34
13
14
19
24
30
35
14
14
20
25
30
36
14
15
21
26
31
37
92
92
5.8
8.7
15.4
20
15.4
20
92
11.5
17.3
23.1
28.9
—
17.6
20
92
24.9
25
92
32.1
35
92
39.4
40
92
—
16.2
20
105
105
105
105
105
105
105
93
5.8
8.7
16.2
20
16.2
20
11.5
17.3
23.1
28.9
—
18.6
20
25.9
30
33.1
35
40.4
45
460-3-60
414
506
9.6
75
0.8
16.0
20
5.8
8.7
16.0
20
93
16.0
20
93
11.5
17.3
23.1
28.9
—
18.4
20
93
07
(cont)
25.6
30
93
32.9
35
93
40.1
45
93
0.6
16.8
20
106
106
106
106
106
106
106
67
5.8
8.7
16.8
20
16.8
20
11.5
17.3
23.1
28.9
—
19.4
20
26.6
30
33.9
35
41.1
45
12.3
15
9.2
14.0
15
67
13.9
18.5
23.1
27.7
—
19.9
20
67
Low
High
Low
High
2.0
2.8
2.0
2.8
25.6
30
67
31.4
35
67
37.1
40
67
—
13.1
15
78
9.2
15.0
15
78
13.9
18.5
23.1
27.7
—
20.9
25
78
26.6
30
78
32.4
35
78
38.1
40
78
575-3-60
518
633
7.6
54
0.8
13.7
15
69
9.2
15.8
20
69
13.9
18.5
23.1
27.7
—
21.6
25
69
27.4
30
69
33.1
35
69
38.9
40
69
1.4
14.5
15
80
9.2
16.8
20
80
13.9
18.5
23.1
27.7
22.6
25
80
28.4
30
80
34.1
35
80
39.9
40
80
E xamp le : Sup p ly voltag e is 2 3 0 --- 3 --- 6 0
LEGEND
FLA
--- Ful l Lo a d A mp s
AB = 224 v
BC = 231 v
AC = 226 v
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
224 + 231 + 226
3
LRA --- Lo ck e d R o t o r A mp s
Average Voltage =
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
681
3
=
=
227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power
distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-
ingly.
{
Fuse or HACR circuit breaker.
4
NOTES:
% Voltage Imbalance
=
100 x
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
227
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percentage of voltage imbalance.
utility company immediately.
max voltage deviation from average voltage
% Voltage Imbalance
= 100 x
average voltage
16
Table 3 – Electrical Data -- Units With Optional Powered Convenience Outlet
VOLTAGE
RANGE
DISCONNECT
SIZE
NOMINAL
COMPRESSOR
ELECTRIC HEAT
POWER SUPPLY
OFM
FLA
IFM
POWER
EXHAUST
FLA
UNIT
50PG
IFM
FLA
POWER SUPPLY
Nominal
TYPE
Min
Max
RLA
LRA
FLA
MCA
MOCP†
FLA
LRA
Volts-Ph-Hz
kW*
—
—
26.7/26.7
26.7/27.8
33.8/37.1
44.6/49.6
55.5/62.1
26.7/26.7
26.7/27.8
33.8/37.1
44.6/49.6
55.5/62.1
28.1/28.1
28.1/29.5
35.5/38.9
46.4/51.4
57.3/63.9
28.1/28.1
28.1/29.5
35.5/38.9
46.4/51.4
57.3/63.9
30.0/30.0
30.0/30.0
33.8/37.1
44.6/49.6
55.5/62.1
77.1/87.1
30.0/30.0
30.0/30.0
33.8/37.1
44.6/49.6
55.5/62.1
77.1/87.1
31.4/31.4
31.4/31.4
35.5/38.9
46.4/51.4
57.3/63.9
78.9/88.9
31.4/31.4
31.4/31.4
35.5/38.9
46.4/51.4
57.3/63.9
78.9/88.9
25.1/25.1
25.1/25.1
25.1/26.5
30.9/33.8
37.1/41.0
49.6/55.4
25.1/25.1
25.1/25.1
25.1/26.5
30.9/33.8
37.1/41.0
49.6/55.4
30/30
30/30
35/40
45/50
60/70
30/30
30/30
35/40
45/50
60/70
30/30
30/30
40/40
50/60
60/70
30/30
30/30
40/40
50/60
60/70
30/30
30/30
35/40
45/50
60/70
80/90
30/30
30/30
35/40
45/50
60/70
80/90
35/35
35/35
40/40
50/60
60/70
80/90
35/35
35/35
40/40
50/60
60/70
80/90
30/30
30/30
30/30
35/35
40/45
50/60
30/30
30/30
30/30
35/35
40/45
50/60
27/27
27/27
31/34
41/46
51/57
27/27
27/27
31/34
41/46
51/57
29/29
29/29
33/36
43/47
53/59
29/29
29/29
33/36
43/47
53/59
30/30 102/102
30/30 102/102
31/34 102/102
41/46 102/102
51/57 102/102
71/80 102/102
30/30 102/102
30/30 102/102
31/34 102/102
41/46 102/102
51/57 102/102
71/80 102/102
32/32 104/104
32/32 104/104
33/36 104/104
43/47 104/104
53/59 104/104
73/82 104/104
32/32 104/104
32/32 104/104
33/36 104/104
43/47 104/104
53/59 104/104
73/82 104/104
79/79
79/79
79/79
79/79
79/79
79/79
79/79
79/79
79/79
79/79
81/81
81/81
81/81
81/81
81/81
81/81
81/81
81/81
81/81
81/81
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
—
Low
High
Low
High
—
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
—
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
—
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
—
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
52.0/60.0
—
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
52.0/60.0
—
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
52.0/60.0
—
10.8/12.5
17.3/20.0
26.0/30.0
34.7/40.0
52.0/60.0
—
6.3/ 7.2
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
—
03
208/230-1-60
187
253
12.8
60
1.0
4.9
1.4
Low
High
Low
High
Low
High
—
1.4
—
208/230-1-60
187
253
15.4
83
1.0
4.9
04
26/26
26/26
26/26
28/31
34/38
46/51
26/26
26/26
26/26
28/31
34/38
46/51
96/96
96/96
96/96
96/96
96/96
96/96
96/96
96/96
96/96
96/96
96/96
96/96
208/230-3-60
187
253
11.5
77
1.0
4.9
6.3/ 7.2
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
E xamp le : Sup p ly voltag e is 2 3 0 --- 3 --- 6 0
LEGEND
FLA
--- Ful l Lo a d A mp s
AB = 224 v
BC = 231 v
AC = 226 v
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
224 + 231 + 226
3
LRA --- Lo ck e d R o t o r A mp s
Average Voltage =
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
681
3
=
=
227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power
distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-
ingly.
{
Fuse or HACR circuit breaker.
4
NOTES:
% Voltage Imbalance
=
100 x
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
227
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percentage of voltage imbalance.
utility company immediately.
max voltage deviation from average voltage
% Voltage Imbalance
= 100 x
average voltage
17
Table 3 -- Electrical Data -- Units With Optional Powered Convenience Outlet (cont)
VOLTAGE
DISCONNECT
SIZE
NOMINAL
COMPRESSOR
ELECTRIC HEAT
POWER SUPPLY
OFM
FLA
IFM
POWER
EXHAUST
FLA
RANGE
UNIT
50PG
IFM
FLA
POWER SUPPLY
Nominal
TYPE
Min
Max
RLA
LRA
FLA
MCA
MOCP†
FLA
LRA
Volts-Ph-Hz
kW*
—
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
—
26.5/26.5
26.5/26.5
26.5/28.3
32.6/35.5
38.9/42.8
51.4/57.1
26.5/26.5
26.5/26.5
26.5/28.3
32.6/35.5
38.9/42.8
51.4/57.1
11.2
30/30
30/30
30/30
35/40
40/45
60/60
30/30
30/30
30/30
35/40
40/45
60/60
15
27/27
27/27
27/27
30/33
36/39
47/53
27/27
27/27
27/27
30/33
36/39
47/53
11
98/98
98/98
98/98
98/98
98/98
98/98
98/98
98/98
98/98
98/98
98/98
98/98
44
6.3/ 7.2
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
—
Low
High
Low
High
Low
High
208/230-3-60
187
414
518
187
253
11.5
77
1.0
0.5
0.5
1.0
1.4
4.9
2.1
2.1
6.3/ 7.2
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
—
2.3/ 3.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
—
3.5
3.0
11.2
15
11
44
5.8
5.0
12.6
15
12
44
8.7
7.5
16.3
20
15
44
11.5
10.0
15.0
—
19.8
20
18
44
17.3
27.0
30
25
44
—
—
11.2
15
11
44
3.5
3.0
11.2
15
11
44
5.8
5.0
12.6
15
12
44
8.7
7.5
16.3
20
15
44
11.5
10.0
15.0
—
19.8
20
18
44
04
17.3
27.0
30
25
44
460-3-60
506
633
253
5.1
35
(cont)
—
11.8
15
12
45
3.5
3.0
11.8
15
12
45
5.8
5.0
13.4
15
12
45
8.7
7.5
17.0
20
16
45
11.5
10.0
15.0
—
20.5
25
19
45
17.3
27.8
30
26
45
0.6
—
11.8
15
12
45
3.5
3.0
11.8
15
12
45
5.8
5.0
13.4
15
12
45
8.7
7.5
17.0
20
16
45
11.5
10.0
15.0
—
20.5
25
19
45
17.3
27.8
30
26
45
—
9.7
15
10
39
9.2
10.0
15.0
—
16.3
20
15
39
Low
High
Low
High
13.9
22.1
25
20
39
—
—
9.7
15
10
39
9.2
10.0
15.0
—
16.3
20
15
39
13.9
22.1
25
20
39
575-3-60
4.3
31
—
11.1
15
12
41
9.2
10.0
15.0
—
18.0
20
17
41
13.9
23.9
25
22
41
1.4
—
11.1
15
12
41
9.2
10.0
15.0
—
18.0
20
17
41
13.9
23.9
25
22
41
—
36.3/ 36.3
40/ 40 36/ 36 128/128
40/ 40 36/ 36 128/128
45/ 50 41/ 46 128/128
60/ 70 51/ 57 128/128
80/ 90 71/ 80 128/128
17.3/20.0
26.0/30.0
34.7/40.0
52.0/60.0
69.3/80.0
—
3.8/ 5.0 36.3/ 37.1
5.6/ 7.5 44.6/ 49.6
7.5/10.0 55.5/ 62.1
11.3/15.0 77.1/ 87.1
Low
High
Low
High
Low
High
Low
High
4.9
7.0
4.9
7.0
4.9
5.2
4.9
5.2
15.0/20.0 98.8/112.1 100/125 91/103 128/128
—
1.4
—
—
38.4/ 38.4
38.4/ 39.8
47.3/ 52.3
58.1/ 64.8
79.8/ 89.8
40/ 40 38/ 38 153/153
40/ 40 38/ 38 153/153
50/ 60 43/ 48 153/153
60/ 70 53/ 60 153/153
80/ 90 73/ 83 153/153
17.3/20.0
26.0/30.0
34.7/40.0
52.0/60.0
69.3/80.0
—
17.3/20.0
26.0/30.0
34.7/40.0
52.0/60.0
69.3/80.0
—
17.3/20.0
26.0/30.0
34.7/40.0
52.0/60.0
69.3/80.0
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0 101.4/114.8 110/125 93/106 153/153
208/230-1-60
20.5
109
—
37.7/ 37.7
37.7/ 38.9
46.4/ 51.4
57.3/ 63.9
78.9/ 88.9
40/ 40 37/ 37 130/130
40/ 40 37/ 37 130/130
50/ 60 43/ 47 130/130
60/ 70 53/ 59 130/130
80/ 90 73/ 82 130/130
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0 100.5/113.9 110/125 92/105 130/130
—
39.8/ 39.8
39.8/ 41.5
49.0/ 54.0
59.9/ 66.5
81.5/ 91.5
40/ 40 40/ 40 155/155
40/ 45 40/ 40 155/155
50/ 60 45/ 50 155/155
60/ 70 55/ 61 155/155
90/100 75/ 84 155/155
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0 103.1/116.5 110/125 95/107 155/155
05
—
29.0/29.0
29.0/29.0
30.9/33.8
37.1/41.0
49.6/55.4
62.1/69.9
29.3/29.3
29.3/29.3
31.3/34.1
37.5/41.4
50.0/55.8
62.5/70.3
30.4/30.4
30.4/30.4
32.6/35.5
38.9/42.8
51.4/57.1
63.9/71.6
30.7/30.7
30.7/30.7
33.0/35.9
39.3/43.1
51.8/57.5
64.3/72.0
30/30
30/30
35/35
40/45
50/60
70/70
30/30
30/30
35/35
40/45
60/60
70/80
35/35
35/35
35/40
40/45
60/60
70/80
35/35
35/35
35/40
40/45
60/60
70/80
29/29 110/110
29/29 110/110
29/31 110/110
34/38 110/110
46/51 110/110
57/64 110/110
29/29 128/128
29/29 128/128
29/31 128/128
35/38 128/128
46/51 128/128
58/65 128/128
31/31 112/112
31/31 112/112
31/33 112/112
36/39 112/112
47/53 112/112
59/66 112/112
31/31 130/130
31/31 130/130
31/33 130/130
36/40 130/130
48/53 130/130
59/66 130/130
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
208/230-3-60
187
253
14.6
91
1.0
1.4
* See Legend on next page.
18
Table 3 -- Electrical Data -- Units With Optional Powered Convenience Outlet (cont)
VOLTAGE
DISCONNECT
SIZE
NOMINAL
COMPRESSOR
ELECTRIC HEAT
POWER SUPPLY
OFM
FLA
POWER
EXHAUST
FLA
IFM
RANGE
UNIT
50PG
POWER SUPPLY
IFM
FLA
Nominal
TYPE
Min
Max
RLA
LRA
FLA
MCA
MOCP†
FLA
LRA
Volts-Ph-Hz
kW*
—
5.8
—
5.0
13.7
13.7
15
15
14
14
15
18
25
32
14
14
16
19
25
32
14
14
16
19
26
32
15
15
16
19
26
33
11
15
20
26
11
15
20
26
12
17
22
27
12
16
22
27
55
55
55
55
55
55
64
64
64
64
64
64
56
56
56
56
56
56
65
65
65
65
65
65
42
42
42
42
48
48
48
48
44
44
44
44
50
50
50
50
8.7
7.5
16.3
20
Low
High
Low
High
2.1
2.6
2.1
2.6
11.5
10.0
15.0
20.0
—
5.0
7.5
10.0
15.0
20.0
—
5.0
7.5
10.0
15.0
20.0
—
5.0
7.5
10.0
15.0
20.0
—
10.0
15.0
20.0
—
10.0
15.0
20.0
—
10.0
15.0
20.0
—
10.0
15.0
20.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
19.8
20
17.3
27.0
30
23.1
34.3
35
—
—
14.2
15
5.8
14.2
15
8.7
16.9
20
11.5
20.4
25
17.3
27.6
30
23.1
34.9
35
460-3-60
414
506
7.1
46
0.5
—
14.3
15
5.8
14.3
15
8.7
17.0
20
11.5
20.5
25
17.3
27.8
30
23.1
35.0
40
0.6
—
14.8
15
05
(cont)
5.8
14.8
15
8.7
17.6
20
11.5
21.1
25
17.3
28.4
30
23.1
35.6
40
—
10.7
15
9.2
16.3
20
Low
High
Low
High
2.1
2.0
2.1
2.0
13.9
22.1
25
18.5
27.9
30
—
—
10.6
15
9.2
16.1
20
13.9
22.0
25
18.5
27.8
30
575-3-60
518
633
5.1
34
0.5
—
12.1
15
9.2
18.0
20
13.9
23.9
25
18.5
29.6
30
1.4
—
12.0
15
9.2
17.9
20
13.9
23.8
25
18.5
29.5
30
—
44.8/ 44.8
44.8/ 44.8
44.8/ 49.6
55.5/ 62.1
77.1/ 87.1
50/ 50
50/ 50
50/ 50
60/ 70
80/ 90
44/44 165/165
44/44 165/165
44/46 165/165
51/57 165/165
71/80 165/165
91/103 165/165
17.3/ 20.0
26.0/ 30.0
34.7/ 40.0
52.0/ 60.0
69.3/ 80.0
86.7/100.0
—
Low
High
Low
High
4.9
7.0
4.9
7.0
98.8/112.1 100/125
18.8/25.0 120.5/137.1 125/150 111/126 165/165
—
—
46.9/ 46.9
46.9/ 46.9
47.3/ 52.3
58.1/ 64.8
79.8/ 89.8
50/ 50
50/ 50
50/ 60
60/ 70
80/ 90
46/ 46 190/190
46/ 46 190/190
46/ 48 190/190
53/ 60 190/190
73/ 83 190/190
93/106 190/190
17.3/ 20.0
26.0/ 30.0
34.7/ 40.0
52.0/ 60.0
69.3/ 80.0
86.7/100.0
—
17.3/ 20.0
26.0/ 30.0
34.7/ 40.0
52.0/ 60.0
69.3/ 80.0
86.7/100.0
—
17.3/ 20.0
26.0/ 30.0
34.7/ 40.0
52.0/ 60.0
69.3/ 80.0
86.7/100.0
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0 101.4/114.8 110/125
18.8/25.0 123.1/139.8 125/150 113/129 190/190
06
208/230-1-60
187
253
26.9
145
1.5
—
46.2/ 46.2
46.2/ 46.2
46.4/ 51.4
57.3/ 63.9
78.9/ 88.9
50/ 50
50/ 50
50/ 60
60/ 70
80/ 90
45/ 45 167/167
45/ 45 167/167
45/ 47 167/167
53/ 59 167/167
73/ 82 167/167
92/105 167/167
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0 100.5/113.9 110/125
18.8/25.0 122.3/138.9 125/150 112/128 167/167
1.4
—
48.3/ 48.3
48.3/ 48.3
49.0/ 54.0
59.9/ 66.5
81.5/ 91.5
50/ 50
50/ 50
50/ 60
60/ 70
90/100
48/ 48 192/192
48/ 48 192/192
48/ 50 192/192
55/ 61 192/192
75/ 84 192/192
95/107 192/192
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0 103.1/116.5 110/125
18.8/25.0 124.9/141.5 125/150 115/130 192/192
E xamp le : Sup p ly voltag e is 2 3 0 --- 3 --- 6 0
LEGEND
FLA
--- Ful l Lo a d A mp s
AB = 224 v
BC = 231 v
AC = 226 v
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
224 + 231 + 226
3
LRA --- Lo ck e d R o t o r A mp s
Average Voltage =
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
681
3
=
=
227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power
distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-
ingly.
{
Fuse or HACR circuit breaker.
4
NOTES:
% Voltage Imbalance
=
100 x
227
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percentage of voltage imbalance.
max voltage deviation from average voltage
% Voltage Imbalance
= 100 x
average voltage
19
Table 3 -- Electrical Data -- Units With Optional Powered Convenience Outlet (cont)
VOLTAGE
DISCONNECT
SIZE
NOMINAL
COMPRESSOR
ELECTRIC HEAT
POWER SUPPLY
OFM
FLA
POWER
EXHAUST
FLA
IFM
RANGE
POWER SUPPLY
UNIT
50PG
IFM
FLA
Nominal
TYPE
Min
Max
RLA
LRA
FLA
MCA
MOCP†
FLA
LRA
Volts-Ph-Hz
kW*
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
33.5/33.5
33.5/33.5
33.5/34.1
37.5/41.4
50.0/55.8
62.5/70.3
75.0/84.6
33.5/33.5
33.5/33.5
33.5/34.1
37.5/41.4
50.0/55.8
62.5/70.3
75.0/84.6
34.9/34.9
34.9/34.9
34.9/35.9
39.3/43.1
51.8/57.5
64.3/72.0
76.8/86.4
34.9/34.9
34.9/34.9
34.9/35.9
39.3/43.1
51.8/57.5
64.3/72.0
76.8/86.4
15.2
35/35
35/35
35/35
40/45
60/60
70/80
80/90
35/35
35/35
35/35
40/45
60/60
70/80
80/90
35/35
35/35
35/40
40/45
60/60
70/80
80/90
35/35
35/35
35/40
40/45
60/60
70/80
80/90
20
33/33 161/161
33/33 161/161
33/33 161/161
35/38 161/161
46/51 161/161
58/65 161/161
69/78 161/161
33/33 161/161
33/33 161/161
33/33 161/161
35/38 161/161
46/51 161/161
58/65 161/161
69/78 161/161
35/35 163/163
35/35 163/163
35/35 163/163
36/40 163/163
48/53 163/163
59/66 163/163
71/79 163/163
35/35 163/163
35/35 163/163
35/35 163/163
36/40 163/163
48/53 163/163
59/66 163/163
71/79 163/163
Low
High
Low
High
Low
High
Low
High
—
1.4
—
208/230-3-60
187
253
17.6
123
1.5
5.2
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
15
15
16
19
25
32
39
15
15
16
19
25
32
39
16
16
16
19
26
33
39
16
16
16
19
26
33
39
12
15
20
26
31
12
15
20
26
31
14
16
22
27
32
14
16
22
27
32
69
69
69
69
69
69
69
69
69
69
69
69
69
69
70
70
70
70
70
70
70
70
70
70
70
70
70
70
55
55
55
55
55
55
55
55
55
55
57
57
57
57
57
57
57
57
57
57
5.8
5.0
15.2
20
8.7
7.5
16.9
20
11.5
10.0
20.4
25
17.3
15.0
27.6
30
23.1
20.0
34.9
35
28.9
25.0
42.1
45
—
—
15.2
20
5.8
5.0
15.2
20
06
(cont)
8.7
7.5
16.9
20
11.5
10.0
20.4
25
17.3
15.0
27.6
30
23.1
20.0
34.9
35
28.9
25.0
42.1
45
460-3-60
414
506
7.7
50
0.8
2.6
—
—
15.8
20
5.8
5.0
15.8
20
8.7
7.5
17.6
20
11.5
10.0
21.1
25
17.3
15.0
28.4
30
23.1
20.0
35.6
40
28.9
25.0
42.9
45
0.6
—
—
15.8
20
5.8
5.0
15.8
20
8.7
7.5
17.6
20
11.5
10.0
21.1
25
17.3
15.0
28.4
30
23.1
20.0
35.6
40
28.9
25.0
42.9
45
—
—
12.1
15
9.2
10.0
16.1
20
13.9
15.0
22.0
25
Low
High
Low
High
18.5
20.0
27.8
30
23.1
25.0
33.5
35
—
—
—
12.1
15
9.2
10.0
16.1
20
13.9
15.0
22.0
25
18.5
20.0
27.8
30
23.1
25.0
33.5
35
575-3-60
518
633
6.1
40
0.8
2.0
—
—
13.5
15
9.2
10.0
17.9
20
13.9
15.0
23.8
25
18.5
20.0
29.5
30
23.1
25.0
35.3
40
1.4
—
—
13.5
15
9.2
10.0
17.9
20
13.9
15.0
23.8
25
18.5
20.0
29.5
30
23.1
25.0
35.3
40
—
—
37.1/37.1
37.1/37.1
37.1/37.1
37.5/41.4
50.0/55.8
62.5/70.3
75.0/84.6
39.4/39.4
39.4/39.4
39.4/39.4
40.4/44.3
52.9/58.6
65.4/73.1
77.9/87.5
40/40
40/40
40/40
40/45
60/60
70/80
80/90
40/40
40/40
40/40
45/45
60/60
70/80
80/90
37/37 187/187
37/37 187/187
37/37 187/187
37/38 187/187
46/51 187/187
58/65 187/187
69/78 187/187
39/39 213/213
39/39 213/213
39/39 213/213
39/41 213/213
49/54 213/213
60/67 213/213
72/81 213/213
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
Low
5.2
7.5
07
208/230-3-60
187
253
20.5
149
1.5
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
High
* See Legend on next page.
20
Table 3 -- Electrical Data -- Units With Optional Powered Convenience Outlet (cont)
VOLTAGE
DISCONNECT
SIZE
NOMINAL
COMPRESSOR
ELECTRIC HEAT
POWER SUPPLY
OFM
FLA
IFM
POWER
EXHAUST
FLA
RANGE
UNIT
50PG
IFM
FLA
POWER SUPPLY
Nominal
TYPE
Min
Max
RLA
LRA
FLA
MCA
MOCP†
FLA
LRA
Volts-Ph-Hz
kW*
—
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
3.8/ 5.0
5.6/ 7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
—
5.0
7.5
10.0
15.0
20.0
25.0
—
5.0
7.5
10.0
15.0
20.0
25.0
—
5.0
7.5
10.0
15.0
20.0
25.0
—
5.0
7.5
10.0
15.0
20.0
25.0
—
10.0
15.0
20.0
25.0
30.0
—
10.0
15.0
20.0
25.0
30.0
—
10.0
15.0
20.0
25.0
30.0
—
10.0
15.0
20.0
25.0
30.0
38.5/38.5
38.5/38.5
38.5/38.5
39.3/43.1
51.8/57.5
64.3/72.0
76.8/86.4
40.8/40.8
40.8/40.8
40.8/40.8
42.1/46.0
54.6/60.4
67.1/74.9
79.6/89.3
17.6
40/40
40/40
40/40
40/45
60/60
70/80
80/90
45/45
45/45
45/45
45/50
60/70
70/80
80/90
20
38/38 189/189
38/38 189/189
38/38 189/189
38/40 189/189
48/53 189/189
59/66 189/189
71/79 189/189
41/41 215/215
41/41 215/215
41/41 215/215
41/42 215/215
50/56 215/215
62/69 215/215
73/82 215/215
Low
High
Low
High
Low
High
5.2
7.5
2.6
3.4
2.6
3.4
208/230-3-60
187
253
20.5
149
1.5
1.4
10.0/11.5
15.0/17.3
20.0/23.1
30.0/34.6
40.0/46.2
50.0/57.7
—
17
17
17
19
25
32
39
18
18
18
20
26
33
40
18
18
18
19
26
33
39
19
19
19
20
27
34
40
14
15
20
26
31
36
15
16
21
26
32
37
16
16
22
27
32
38
16
17
23
28
33
39
94
94
5.8
8.7
17.6
20
17.6
20
94
11.5
17.3
23.1
28.9
—
20.4
25
94
27.6
30
94
34.9
35
94
42.1
45
94
—
18.4
20
107
107
107
107
107
107
107
95
5.8
8.7
18.4
20
18.4
20
11.5
17.3
23.1
28.9
—
21.4
25
28.6
30
35.9
40
43.1
45
460-3-60
414
506
9.6
75
0.8
18.2
20
5.8
8.7
18.2
20
95
18.2
20
95
11.5
17.3
23.1
28.9
—
21.1
25
95
07
(cont)
28.4
30
95
35.6
40
95
42.9
45
95
0.6
19.0
20
108
108
108
108
108
108
108
69
5.8
8.7
19.0
20
19.0
20
11.5
17.3
23.1
28.9
—
22.1
25
29.4
30
36.6
40
43.9
45
14.0
15
9.2
16.1
20
69
13.9
18.5
23.1
27.7
—
22.0
25
69
Low
High
Low
High
2.0
2.8
2.0
2.8
27.8
30
69
33.5
35
69
39.3
40
69
—
14.8
15
80
9.2
17.1
20
80
13.9
18.5
23.1
27.7
—
23.0
25
80
28.8
30
80
34.5
35
80
40.3
45
80
575-3-60
518
633
7.6
54
0.8
15.4
20
71
9.2
17.9
20
71
13.9
18.5
23.1
27.7
—
23.8
25
71
29.5
30
71
35.3
40
71
41.0
45
71
1.4
16.2
20
82
9.2
18.9
20
82
13.9
18.5
23.1
27.7
24.8
25
82
30.5
35
82
36.3
40
82
42.0
45
82
E xamp le : Sup p ly voltag e is 2 3 0 --- 3 --- 6 0
LEGEND
FLA
--- Ful l Lo a d A mp s
AB = 224 v
BC = 231 v
AC = 226 v
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
224 + 231 + 226
3
LRA --- Lo ck e d R o t o r A mp s
Average Voltage =
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
681
3
=
=
227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power
distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-
ingly.
{
Fuse or HACR circuit breaker.
4
NOTES:
% Voltage Imbalance
=
100 x
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
227
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percentage of voltage imbalance.
utility company immediately.
max voltage deviation from average voltage
% Voltage Imbalance
= 100 x
average voltage
21
4. Hang the barometric relief/power exhaust hood on the
mounting flange on the economizer panel. Secure hood to
panel with screws saved from Step 2. (See Fig. 15 and 16.)
Step 7 — Install Outdoor Air Hoods (Units with
Economizer)
Perform the following procedure to install the outdoor--air hoods:
5. Align hole in flange of economizer panel with left edge of
hood. Hang economizer hood on the top flange of the
economizer panel by rotating hood until top flange of the
economizer hood engages the bent flange on the
economizer panel. Rotate hood until hood is flush with the
economizer panel. Hood will support itself from flange.
Align holes in hood with holes in panel and secure hood to
panel with screws saved from Step 2. (See Fig. 16 and 17.)
1. Economizer and barometric relief hoods are located in the
condenser section under the slanted coil for shipping. (See
Fig. 14.) Barometric relief/power exhaust hood is shipped
inside of economizer hood. Remove screws that secure the
wooden rails of the hood assemblies to the unit. Save
screws. Slide complete assembly from condenser section.
2. Remove the screws that secure the economizer and
barometric relief/power exhaust hoods to the wooden
railing. Discard or recycle wooden rails. Save screws.
Step 8 — Install All Accessories
After all of the factory--installed options have been adjusted, install
all field--installed accessories. Refer to the accessory installation
instructions included with each accessory. Consult the Carrier Price
Pages for accessory package numbers for particular applications.
3. The barometric relief damper is factory mounted onto the
economizer panel for shipping. Remove the screw holding
the barometric relief damper to the panel. Damper should be
free to swing open during operation. (See Fig. 15.)
POWER EXHAUST/
BAROMETRIC
RELIEF HOOD
POWER EXHAUST/
BAROMETRIC
RELIEF HOOD
MOUNTING
FLANGE
ECONOMIZER
WOODEN RAILS
HOOD
C06262
Fig. 16 -- Barometric Relief/Power Exhaust
Hood Flange
C06290
Fig. 14 -- Economizer and Baromatric
Relief/Power Exhaust Hoods Shipping Positions
MOUNTING
FLANGE
ECONOMIZER
HOOD
ECONOMIZER
HOOD
POWER EXHAUST/
BAROMETRIC
RELIEF HOOD
BAROMETRIC
ECONOMIZER
RELIEF DAMPER SCREW
PANEL
C06260
Fig. 15 -- Hood Installation
C06263
Fig. 17 -- Economizer Flange
Catalog No:50PG---40SI
Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 03/10
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: 50PG---36SI
22
|
Cecilware Liquid Iced Tea Dispenser TT1 User Manual
Chromalox UB 1252E User Manual
Craftsman 7174295 User Manual
Epson Printer 810 User Manual
Epson Printer FX 880+ User Manual
Fisher Price M7933 User Manual
Friedrich 30 User Manual
Friedrich ZQ08A10C User Manual
Fujitsu fi 434PR User Manual
Honda Automobiles GXV670 User Manual